Fronius IG 300 Manuel d'utilisateur Page 56

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 80
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 55
48
AC leads and a
pair of DC leads
3
L
1
L
2
L
3
N
P
E
P
E
1
2
AC leads and a
two pairs of DC
leads
- AC cable cross section: 35 mm²
The copper brackets on the DC side
provide enough space for up to 8 DC
cables. The fitting screws are supplied
with the FRONIUS IG.
NOTE! Do not exceed the follo-
wing torques when tightening the
screws:
- AC terminals: 6 Nm
- Securing the DC cables to
the copper brackets: 30 Nm
(M12 screws)
- AC cable cross section: 35 mm²
- DC cable cross section: 70 mm²
If two pairs of DC cables are connected to
the FRONIUS IG, they should be con-
nected directly (without using the copper
brackets).
NOTE! Do not exceed the follo-
wing torques when tightening the
screws:
- AC terminals: 6 Nm
- DC terminals: 7 Nm
- After connecting the cable, replace
the cover
AC
DC
+
-
L1, L2, L3, N, PE
Strain relief Open the strain relief device, remove it if
necessary and route the following cables
through it:
- AC cable
- DC cable
- Cables for LocalNet/DatCom if they
are installed (additionally secure these
with cable ties)
- Cables for external power supply to
the rack, if installed
1
1
2
1
3
Important! If required, request a sealing cover for the over/undervoltage relay and have
it fitted by your power supply company.
L
1
L
2
L
3
N
P
E
P
E
2
2
1
AC
DC
+
-
L1, L2, L3, N, PE