Fronius IG 300 Manuel d'utilisateur Page 66

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 80
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 65
58
Following careful testing
and when the mains fre-
quency passes into the per-
missible range, the FRONI-
US IG will resume feeding
power into the mains.
134 Mains frequency in
phase 3 outside the
permissible range
Check mains frequency
If this service code keeps
recurring, contact your
system engineer
Following careful testing
and when the mains condi-
tions are within the permis-
sible range again, the FRO-
NIUS IG will resume feeding
power into the mains.
107 No AC network Check mains connec-
tions and fuses
If this service code keeps
recurring, contact your
system engineer
Following careful testing
and when the mains condi-
tions are within the permis-
sible range again, the FRO-
NIUS IG will resume feeding
power into the mains.
108 Islanding detected If this service code keeps
recurring, contact your
system engineer
No power is fed into the
mains
109 General mains fault If this service code keeps
recurring, contact your
system engineer
Class 1
(continued)
Class 2 service codes can only occur in connection with the optional overvoltage/under-
voltage relay.
Class 2 service codes are also related to the mains parameters. Therefore, some of the
testing methods overlap with those for service class 1. The FRONIUS IG will react in
exactly the same way as with class 1 service codes.
Code Designation Manifestation Remedy
No power is fed into the
mains
The overvoltage/undervol-
tage relay has tripped
210 Mains contactor open If this service code keeps
recurring, contact your
system engineer
Class 2
Code Designation Manifestation Remedy
Vue de la page 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 79 80

Commentaires sur ces manuels

Pas de commentaire